ML
    • Recent
    • Categories
    • Tags
    • Popular
    • Users
    • Groups
    • Register
    • Login

    Odd Shaped Power Bricks and UPS

    IT Discussion
    9
    29
    2.5k
    Loading More Posts
    • Oldest to Newest
    • Newest to Oldest
    • Most Votes
    Reply
    • Reply as topic
    Log in to reply
    This topic has been deleted. Only users with topic management privileges can see it.
    • BRRABillB
      BRRABill
      last edited by

      The problem(s) I have is ...

      1. the current server room is poorly wired with access to electrical boxes
      2. some of the equipment I have in there has strange "the wrong way" power blocks

      I could re-use an older UPS, I guess. I'm just wondering, as I said, what others are doing.

      dafyreD 1 Reply Last reply Reply Quote 0
      • J
        Jason Banned
        last edited by

        What in the server room has wall warts? Most things use IEC cables direct or a Brick with an IEC to it.

        BRRABillB 1 Reply Last reply Reply Quote 0
        • dafyreD
          dafyre @BRRABill
          last edited by

          @BRRABill said in Odd Shaped Power Bricks and UPS:

          The problem(s) I have is ...

          1. the current server room is poorly wired with access to electrical boxes
          2. some of the equipment I have in there has strange "the wrong way" power blocks

          I could re-use an older UPS, I guess. I'm just wondering, as I said, what others are doing.

          That's odd. We never got dinged for it at my last job. (Granted, we didn't use the $7 Dollar General special either).

          And at my current job, we use power bars made specifically for use in server racks. (these, I assume have the overcurrent protection, etc, etc).

          BRRABillB 1 Reply Last reply Reply Quote 0
          • BRRABillB
            BRRABill @Jason
            last edited by

            @Jason said in Odd Shaped Power Bricks and UPS:

            What in the server room has wall warts? Most things use IEC cables direct or a Brick with an IEC to it.

            I have a couple of small switches in there with strange wall warts.

            J 1 Reply Last reply Reply Quote 0
            • J
              Jason Banned @BRRABill
              last edited by

              @BRRABill said in Odd Shaped Power Bricks and UPS:

              @Jason said in Odd Shaped Power Bricks and UPS:

              What in the server room has wall warts? Most things use IEC cables direct or a Brick with an IEC to it.

              I have a couple of small switches in there with strange wall warts.

              I would replace the switches then..

              BRRABillB 2 Replies Last reply Reply Quote 0
              • BRRABillB
                BRRABill @dafyre
                last edited by

                @dafyre said in Odd Shaped Power Bricks and UPS:

                @BRRABill said in Odd Shaped Power Bricks and UPS:

                The problem(s) I have is ...

                1. the current server room is poorly wired with access to electrical boxes
                2. some of the equipment I have in there has strange "the wrong way" power blocks

                I could re-use an older UPS, I guess. I'm just wondering, as I said, what others are doing.

                That's odd. We never got dinged for it at my last job. (Granted, we didn't use the $7 Dollar General special either).

                And at my current job, we use power bars made specifically for use in server racks. (these, I assume have the overcurrent protection, etc, etc).

                They haven't checked in a while, and I think maybe they were just looking to ding people.

                I also got dinged for not having ceiling tiles in our wiring room.

                J 1 Reply Last reply Reply Quote 0
                • BRRABillB
                  BRRABill @Jason
                  last edited by

                  @Jason said in Odd Shaped Power Bricks and UPS:

                  @BRRABill said in Odd Shaped Power Bricks and UPS:

                  @Jason said in Odd Shaped Power Bricks and UPS:

                  What in the server room has wall warts? Most things use IEC cables direct or a Brick with an IEC to it.

                  I have a couple of small switches in there with strange wall warts.

                  I would replace the switches then..

                  A definite possibility!

                  1 Reply Last reply Reply Quote 0
                  • DustinB3403D
                    DustinB3403
                    last edited by

                    Or just find a better power adapter for the switch, one that will provide the correct power output, and fit in your UPS.

                    1 Reply Last reply Reply Quote 0
                    • J
                      Jason Banned @BRRABill
                      last edited by Jason

                      @BRRABill said in Odd Shaped Power Bricks and UPS:

                      I also got dinged for not having ceiling tiles in our wiring room.

                      That is normal if you have a drop ceiling. It's for a fire(smoke)/air barrier.

                      1 Reply Last reply Reply Quote 1
                      • gjacobseG
                        gjacobse
                        last edited by

                        I wonder if something of this sort would be allowed.... It's not a power strip. just power cords that are about a foot long to allow connection to the adapters.

                        http://i.stack.imgur.com/8zW2l.jpg

                        J 1 Reply Last reply Reply Quote 1
                        • DashrenderD
                          Dashrender
                          last edited by

                          I bet they would be. I'm sure the primary concern, as Jason rightly pointed out, was the overdrawn issue.

                          1 Reply Last reply Reply Quote 0
                          • J
                            Jason Banned @gjacobse
                            last edited by Jason

                            @gjacobse said in Odd Shaped Power Bricks and UPS:

                            I wonder if something of this sort would be allowed.... It's not a power strip. just power cords that are about a foot long to allow connection to the adapters.

                            http://i.stack.imgur.com/8zW2l.jpg

                            No over current protection. Also this type device in a commerical setting falls under extension cord restrictions, which OSHA only allows temporary use of. Now if they are UL Listed for being plugged into a power strip in that manner it would be allowed.. (hence how C13 extensions are allowed) but otherwise they would have to be plugged directly into a wall outlet.

                            1 Reply Last reply Reply Quote 0
                            • J
                              Jason Banned
                              last edited by

                              EX: https://www.amazon.com/Solid-Cordz-Female-Extension-Cords/dp/B00CG70K78/ref=cm_cr_dp_asin_lnk

                              These are UL listed but likely not for that use.

                              1 Reply Last reply Reply Quote 0
                              • BRRABillB
                                BRRABill
                                last edited by

                                Yeah these particular switches (workgroup Cisco SG-200-8) can't take that sort of plug.

                                1 Reply Last reply Reply Quote 0
                                • DashrenderD
                                  Dashrender
                                  last edited by

                                  I'm assuming @gjacobse is talking about the black cord only.
                                  https://i.imgur.com/oCkdbBE.png

                                  I don't know OSHA law/rules, but there should be no need to check for over current in the black part, it's a 1 to 1 connection. Assuming you plug the 1 to 1 and it's plugged directly into a UPS port, not a power strip like this picture.

                                  gjacobseG J 2 Replies Last reply Reply Quote 0
                                  • gjacobseG
                                    gjacobse @Dashrender
                                    last edited by

                                    @Dashrender said in Odd Shaped Power Bricks and UPS:

                                    I'm assuming @gjacobse is talking about the black cord only.
                                    https://i.imgur.com/oCkdbBE.png

                                    I don't know OSHA law/rules, but there should be no need to check for over current in the black part, it's a 1 to 1 connection. Assuming you plug the 1 to 1 and it's plugged directly into a UPS port, not a power strip like this picture.

                                    Correct. YOu would not use the power strip as you are using an UPS. Just use the cords to connect the adapter to the UPS as normal.

                                    1 Reply Last reply Reply Quote 0
                                    • FATeknollogeeF
                                      FATeknollogee
                                      last edited by

                                      How about one of these Eaton ePDU G3 units? https://powerquality.eaton.com/ePDUG3/default.asp

                                      1 Reply Last reply Reply Quote 0
                                      • nadnerBN
                                        nadnerB
                                        last edited by

                                        I think you've got it going the wrong way around. You should have mains power into the UPS (i.e. from the wall socket). Then IF you have to have a power board, plug that into the UPS. No power boards/strips in between the wall and UPS. Keep it simple. Less things to go pop in the night.

                                        1 Reply Last reply Reply Quote 0
                                        • J
                                          Jason Banned @Dashrender
                                          last edited by

                                          @Dashrender said in Odd Shaped Power Bricks and UPS:

                                          I'm assuming @gjacobse is talking about the black cord only.
                                          https://i.imgur.com/oCkdbBE.png

                                          I don't know OSHA law/rules, but there should be no need to check for over current in the black part, it's a 1 to 1 connection. Assuming you plug the 1 to 1 and it's plugged directly into a UPS port, not a power strip like this picture.

                                          1:1 does not necessarily imply no over current protection is needed.

                                          DashrenderD 1 Reply Last reply Reply Quote -1
                                          • BRRABillB
                                            BRRABill @Jason
                                            last edited by

                                            @Jason said

                                            I would replace the switches then..

                                            Out of curiosity, what is the switch du jour these days? Was a firm decision ever made?

                                            coliverC J 2 Replies Last reply Reply Quote 0
                                            • 1
                                            • 2
                                            • 1 / 2
                                            • First post
                                              Last post